Electrical Safety Standards for LV/MV/HV (Part-1)

$
0
0
Electrical Safety Standards for LV/MV/HV (Part-1)

Electrical Safety Standards for LV/MV/HV (on photo Indonesia's state energy giant - High Voltage Switchyard)

Content

  1. Standard: Western Power Company
  • Standard: New Zealand Electrical Code
  • Standard: ETSA Utilities
  • Standard: UK Power Networks – EI 02-0019
  • 1. Standard: Western Power Company

    Water Safely Clearance on Electrical Fires

    VoltageMinimum distances between a nozzle producing a fog stream of fresh water and a live conductor
    Up to 750 V1.5 Meter
    750 V to 15 KV4.0  Meter
    15 KV to 230 KV5.0 Meter

    Go to Content ↑


    Minimum Approach Distance for Authorized Person

    This is the minimum distance that must be maintained by a person, vehicle or mobile plant.

    VoltageDistance (minimum)
    Up to 1 KV0.7 Meter
    1 V to 6.6 KV0.7 Meter
    6.6 KV to 11 KV0.7 Meter
    11 KV to 22 KV0.7 Meter
    22 KV to 33 KV1.0 Meter
    33 KV to 66 KV1.0 Meter
    66 KV to 132 KV1.2 Meter
    132 KV to 220 KV1.8 Meter
    220 KV to 330 KV3.0 Meter

    Go to Content ↑


    Minimum Approach Distance for Ordinary Person

    VoltageDistance  (min)
    Up to 1 KV3.0 Meter
    1 V to 6.6 KV3.0 Meter
    6.6 KV to 11 KV3.0 Meter
    11 KV to 22 KV3.0 Meter
    22 KV to 33 KV3.0 Meter
    33 KV to 66 KV3.0 Meter
    66 KV to 132 KV3.0 Meter
    132 KV to 220 KV4.5 Meter
    220 KV to 330 KV6.0 Meter

    Go to Content ↑


    Minimum Approach Distance for Vehicle and Plant for Ordinary Person

    VoltageDistance  (min)
    Mobile PlantVehicle
    Up to 1 KV3.0 Meter0.6 Meter
    1 V to 6.6 KV3.0 Meter0.9 Meter
    6.6 KV to 11 KV3.0 Meter0.9 Meter
    11 KV to 22 KV3.0 Meter0.9 Meter
    22 KV to 33 KV3.0 Meter0.9 Meter
    33 KV to 66 KV3.0 Meter2.1 Meter
    66 KV to 132 KV3.0 Meter2.1 Meter
    132 KV to 220 KV3.0 Meter2.9 Meter
    220 KV to 330 KV6.0 Meter3.4 Meter

    Go to Content ↑

    2. Standard: New Zealand Electrical Code

    Min. Safe Distance between Buildings and Overhead Line

    VoltagePoleTower
    11 kV to 33 kV2 Meter2 Meter
    33 kV to 66 kV6 Meter6 Meter
    66 kV and Above8 Meter8 Meter

    Go to Content ↑


    Min. Safe Distance for excavation near Overhead Line

    Description of ClearanceFrom Pole (Min)From Tower (min)
    Excavation in land more than 750mm depth8 Meter12 Meter
    Excavation in land up to750mm depth2.2 to 5 Meter6 to12 Meter
    Excavation in land up to 300mm depth2.2 Meter6 Meter
    Construction near 11KV to 33KV Line2.2 Meter6 Meter
    Construction near 33KV to 66KV Line6 Meter9  Meter
    Construction near 66KV and more8 Meter12 Meter
    Wire Fence near 1KV to 66KV Line2.2 Meter2.2 Meter
    Wire Fence near 66KV and more5 Meter5 Meter

    Go to Content ↑


    Min. Safe Distance for Tower Carin near Electrical Tower

    Description of ClearanceDistance (Min)
    Mobile Carin movement4.0 Meter
    Tower Carin movement4.0 Meter
    Carin movement4.0 Meter
    Moving Activity above height of Tower4.0 Meter
    Hedge Cutter  movement4.0 Meter

    Go to Content ↑


    Min. Safe Vertical Distance above Railway Track

    Description of ClearanceDistance (Min)
    Earthed conductors5.5 Meter
    Stay wires5.5 Meter
    Conductors up to 33 kV6.5 Meter
    Conductors above 33 kV to 220 kV7.5 Meter
    Conductors above 220 kV.8 Meter

    Go to Content ↑


    Min. Distance between two Conductors on Same Supports

    High Voltage CircuitHigh Voltage CircuitDistance  between circuits (min)
    Up to 33 KVUp to 1KV1.0 Meter
    Up to 33 KVMore than 1KV1.2 Meter
    33 KV to 110 KVUp to 1KV1.5 Meter
    33 KV to 110 KVMore than 1KV2.0 Meter
    More than 110 KVAll2.5 Meter

    Go to Content ↑


    Min. Distance between two Conductors on Different Supports

    High Voltage CircuitDistance (min)
    Up to 1 KV0.6 Meter
    1 KV to 33 KV1.2 Meter
    33 KV to 66 KV1.8 Meter
    110 KV2.4 Meter
    More than 220 KV2.8 Meter

    Go to Content ↑


    Min. Safety Distance from Electrical Apparatuses

    Description of ClearanceDistance (min)
    Passage In front of Metal-Clad Switchgear (UP to HV)1.0 Meter wide 2.5 Height
    Passage In rear or side of Metal-Clad Switchgear (UP to HV)1.0 Meter wide 2.2 Height
    Passage at any side of Metal-Clad Switch gear containing Bare conductor (UP to HV)0.8 Meter wide 2.2 Height

    Go to Content ↑


    Min. Approach Distance for Non-Competent Person near exposed Live Parts

    VoltageDistance (min)
    Below 110 kV4.0 Meter
    220 kV and above6.0 Meter

    Go to Content ↑


    Min. Approach Distance for Competent Person near exposed Live Parts

    VoltageDistance (min)
    Below 1 kV0.5 Meter
    11 kV1.5 Meter
    22 kV2.0 Meter
    33 kV2.5 Meter
    66 kV3.0 Meter
    110 kV4.0 Meter
    220 kV and above6.0 Meter

    Go to Content ↑

    3. Standard: ETSA Utilities

    Vertical Clearances between Services

    ServiceLV CableHV Cable
    Common Pipe0.100 Meter0.100 Meter
    Gas Pipe0.200 Meter0.200 Meter
    Sewer Pipe0.300 Meter0.300 Meter
    Water Pipe0.600 Meter0.600 Meter

    Go to Content ↑


    Horizontal Clearances between Services

    ServiceLV CableHV Cable
    Common Pipe0.100 Meter0.100 Meter
    Gas Pipe0.200 Meter0.200 Meter
    Sewer Pipe1.0 Meter1.0 Meter
    Water Pipe0.600 Meter0.600 Meter

    Go to Content ↑

    4. Standard: UK Power Networks – EI 02-0019

    Cable Installation Depths

    VoltageAreaDepth (min)
    Low VoltageFootways, grass verges or private property0.450 Meter
    Carriageways (including road crossings)0.600 Meter
    Normal agricultural land (not deep ploughing)1.0 Meter
    Agricultural land subject to deep ploughing1.2 Meter
    11 KV to 20 KVFootways, grass verges or private property0.600 Meter
    Carriageways (including road crossings)0.750 Meter
    Normal agricultural land (not deep ploughing)1.0 Meter
    Agricultural land subject to deep ploughing1.2 Meter
    33 KV to 132 KVFootways, grass verges or private property0.9 Meter
    Carriageways (including road crossings)0.9 Meter
    Normal agricultural land (not deep ploughing)1.0 Meter
    Agricultural land subject to deep ploughing1.2 Meter
    Auxiliary Multi-core & Multi-pair CablesFootways, grass verges or private property0.450 Meter
    Carriageways (including road crossings)0.600 Meter
    Normal agricultural land (not deep ploughing)1.0 Meter
    Agricultural land subject to deep ploughing1.2 Meter
    On Cable Ladder for LV to HVThe Horizontal clearance between cables on cable ladders2X Dia of Cable of Largest Cable or min 150 mm
    The clearance from a supporting wall20 mm
    The vertical clearance between cables is greater150 mm
    If the number of cables > 4, they are to be installed in a horizontal

    Go to Content ↑


    Minimum Approach Distance of Crane or Moving Part from Live Conductor

    VoltageWithout Safety ObservationFor ordinary Person
    Un insulated portionsInsulated portions
    Up to 1KV2 Meter1.0 Meter3.0 Meter
    11 KV2 Meter1.4 Meter3.0 Meter
    22 KV2.4 Meter2 Meter3.0 Meter
    33 KV2.4 Meter2 Meter3.0 Meter
    66 KV2.8 Meter2 Meter3.0 Meter
    132 KV3.0 Meter3.0 Meter3.0 Meter
    220 KV4.8 Meter4.8 Meter6.0 Meter
    330 KV6.0 Meter6.0 Meter6.0 Meter
    500 KV8.0 Meter8.0 Meter8.0 Meter

    Go to Content ↑


    Minimum Fixed Clearances for Electrical Apparatus (Isolation Points)

    VoltageFixed Clearance
    Up to 11Kv0.320 Meter
    11KV to 33KV0.320 Meter
    33KV to 66KV0.630 Meter
    66KV to 132KV1.1 Meter

    Go to Content ↑